  switch mode power supply drp024v 0 60w 1ba 1 / 13 rev: 00 , 1/10/2011 60 w 1phase cliq ll din rail drp024v 0 60w1 b a summary the new cliq ii drp024v060w1 b a is the latest offering from one of the worlds largest power supply manufacturers - delta. the product offers a nominal output voltage of 24 v, a wide temperature range from - 20c to + 8 0 c and a minimum holdup time of 20 ms. the state - of - the - art design is made to withstand harsh industrial environments. the rugged, ultra - compact metal case is shock and vibration resistant according to iec 60068 - 2. the 60 watts din rail power supply provides overvoltage, overload and thermal protection. due to the wide input voltage range from 85 to 264 v ac , the deltas cliq ii power supply is worldwide usable. it also comes with m ultiple output terminals for fast wiring and easy installation. features: ? ease of wire connection to terminals ? comes with detachable connectors ? overload , overvoltage & thermal protection ? efficiency > 89% ? power boost 150% for 3 seconds ? expected life time: 10 years ? redundancy: yes (with external or ing diode) ? rohs & ip20 compliant ? meet energy star level 5 ? 3 years warranty
switch mode power supply drp024v 0 60w 1ba 2 / 13 rev: 00 , 1/10/2011 technical data 60w1ph input data (1) nominal input voltage and frequency 100 - 240vac / 50 - 60hz voltage range 85 - 264vac (120 C 375 vdc) frequency range 47 - 63hz nominal current 1.5a max @115v ac , 1.0a max @230v ac inrush current limitation. i2t (+25c) typ. < 35a @ 230vac mains buffering at nominal load (typ.) > 20ms @ 115vac, > 125ms @ 230vac turn - on time < 3.0 sec. internal fuse t 3.15 ah / 250v recommended backup fuse: power circuit - breaker characteristic 6a, 10a or 16a : b leakage current < 1ma energy star level v output data (2) nominal output voltage u n / tolerance 24vdc2% setting range of the output voltage 2 4 - 28vdc nominal current 2.5a de - rating above +50c > 50c (2.5% / c ) startup with capacitive loads max 8,000 f at 25c max. power dissipation idling / nominal load approx. 7.4 w efficiency > 89 % typical. residual ripple / peak switching (20 mhz) (at nominal values) < 50mv / < 15 0mvpp. can be connected in parallel for redundancy and increased capacity yes with o r ing diode or redun dancy module surge voltage protection against internal surge voltages yes certification/standards electrical equipment of machines iec60204 - 1 (over voltage category iii) safety transformers for switched - mode power supply units electrical safety (of information technology equipment) tuv bauart to en60950 - 1, ul/c - ul recognized to ul60950 - 1, csa c22.2 no. 60950 - 1, cb scheme to iec60950 - 1 industrial control equipment ul / c - ul listed ul508 and csa c22.2 no. 107.1 - 01, csa to csa c22.2 no.107.1 - 01 (file no. 181564) electronic equipment for use in electrical power installations en50178 / iec62103 safety entry low voltage pelv (en60204), selv (en60950) safe isolation din.vde 0100 - 410 protection against electric shock din 57100 - 410 protection against shock currents, basic requirements for protective separation in electrical equipment vde 0106 - 101 limitation of mains harmonic currents din57100 - 410
switch mode power supply drp024v 0 60w 1ba 3 / 13 rev: 00 , 1/10/2011 general data isolation voltage: input / output type test/routine test input / pe type test/routine test output / pe type test/routine test 4 kvac / 3 kvac 1.5 kvac / 1 .5 kvac 1.5 kvac / 500 vac degree of protection ip2 0 class of protection class i with pe connection mtbf > 1,000,000 h rs . type of housing aluminium (ai5052) dimensions (l / w / h ) 121 mmx 32 mmx 125 mm weight 0.37 kg status indicator led (6) dc output ok yes (green led) climatic data ambient temperature (operating) ambient temperature (storage) - 20c to 8 0 c (> 50c de - rating) - 25c to 85c humidity at 25c, no n - condensing < 95% rh vibration ( non - operating) 10hz to 500hz @ 30 m/ s 2 (3g peak); displacement of 0.35mm; 60min per axis for all x, y, z direction. in acc. with iec 6 8 00 0 - 2 - 6. shock (in all directions) 30g (300m / s 2 ) in all directions according to iec 600 68 - 2 - 27 pollution degree 2 according to en50178 climatic class 3k3 according to en 60721 in conformance with emc guideline 89/336/eec and low voltage directive 73/23/eec emc (electromagnetic compatibility) dinrail 1ac / 24v dc / 2.5a (eoe 11010248 ) immunity to interference according to en 61000 - 6 - 2 ? en 61000 - 4 - 2 1 ) housing discharge of static electricity (esd) contact discharge: air discharge : level 4 8 kv 15 kv ? en 61000 - 4 - 3 1) housing radiate field immunity frequency/field intensity: level 3 80mhz - 1ghz / 10v / m with 1khz tone / 80% modulation ? en 61000 - 4 - 4 1 ) fast transients (burst): 2kv 4) ? en 61000 - 4 - 5 1 ) surge voltage immunity (surge): ? 2kv 3) / 2kv 4) (level 3) ? en 61000 - 4 - 6 1) i/o: ? conducted immunity frequency / u o : level 3 0.15mhz - 80mhz / 10vrms. ? en 61000 - 4 - 11 2) voltage dips input: main buffering > 20ms. noise emission according to en 610 0 0 - 6 - 3 ? emitted radio interface ? radio interference voltage en55011 (en55022) class b 5 en55011 (en55022) class b 5 en55011 corresponds to cispr11 / en55022 corresponds to cispr22 / e n 61000 corresponds to iec 6 1000 1) criterion a: normal operating behavior within the defined limits. 2) criterion b: temporary impairment to operational behavior that is corrected by the device itself. 3) symmetrical: conductor to conductor. 4) asymmetrical: conductor to ground. 5) class b: area of application industry and residential.
switch mode power supply drp024v 0 60w 1ba 4 / 13 rev: 00 , 1/10/2011 numbering for d in rail power supply for example: drp024v060w 1 b a xx x xxxx xxxx x xx xx.product type dr dinrail xx x xxxx xxxx x xx x.model p power supply xx x xxxx xxxx x xx xxxx.voltage 024v 24 voltage xx x xxxx xxxx x xx xxxxwatt 060w 60 watt 120w 120 watt 240w 240 watt 480w 480 watt xx x xxxx xxxx x xx x.phase 1 1 phase 3 3 phase xx x xxxx xxxx x xx xx.variation (eg, customer, material,etc.) b a delta standard C
switch mode power supply drp024v 0 60w 1ba 5 / 13 rev: 00 , 1/10/2011 block diagrams/connections: block diagram of power supply, ? drp024v060w1 b a
switch mode power supply drp024v 0 60w 1ba 6 / 13 rev: 00 , 1/10/2011 engineering data ? derating curve (both of horizontal and vertical) o model: drp024v060w1 b a note: 1 . do not use the device in areas outside of the shaded portion shown in the above graph. internal parts may gradually deteriorate and become damaged. 2 . based on the above graph, if the ambient temperature is greater than 50 c, the output capacity has to be re duced by 2.5% per celsius temperature increase. if not, the device will go into over - temperature protection by switching off i.e. device will go into bouncing mode. it will recover when ambient temperature drops to 50 c or output capacity is reduced as rec ommended in the graph. 3 . if the device has to be mounted in any other direction, please contact your service provider for more details. 4 . in order for the device to function in the manner intended, it is also necessary to observe a lateral spacing of 2cm from other equipments. 5 . depending on the ambient temperature and output capacity of the device, the device housing can be very hot! 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 110% -20 -10 0 10 20 30 40 50 60 70 80 ambient temperature (c) percentage of max load (%)
switch mode power supply drp024v 0 60w 1ba 7 / 13 rev: 00 , 1/10/2011 mecha nical drawing device description (fig. 1) (1) input terminal block connector (2) output terminal block connector (3) dc voltage adjustment potentiometer (4) dc ok control led (green) (5) universal mounting rail system
switch mode power supply drp024v 0 60w 1ba 8 / 13 rev: 00 , 1/10/2011 ? overl oad protection the power supply is provided with an overload protection (olp) function which protects the power supply from possible damage caused by excess current. the power supply also has an over temperature protection (otp) in case overload condition persists for a n extended duration and is below the overload trigger point but > 100% load. typically the overload current ( i ol ) is > i surge (150%) output voltage will start dropping when the power supply reaches max power limit. it will go into bouncing mode when the output reaches uvlo (under voltage point). the output voltage will recover automatically when the overload condition is removed . ? short circuit protection the power supply has a short circuit protection which is in line with the overload protection and activates whenever there is a short across the output voltage. it will go into bouncing mode and recovers automatically wh en the fault is removed. ? over temperature protection the power supply has an over temperature protection (otp). this is activated when the overload condition persists for an extended duration and the output current is below the overload trigger point but >100% load. in the event of a higher ambient operating condition at 100% load, the power supply will run into otp when the ambient temperature is > 55 c. when activated, the output voltage will go into bouncing mode until the operating ambient temper ature drops to 50 c or output capacity is reduced as recommended in the graph.
switch mode power supply drp024v 0 60w 1ba 9 / 13 rev: 00 , 1/10/2011 ? overv oltage protection the power supply has an overvoltage protection (ovp) and is activated when the power supply feedback circuit fails. the output voltage will not be > 35v under any line/load and operating ambient temperature. the power supply does not shut down but goes into hiccup mode (auto - recovery). the output voltage will recover back to 24vdc once the fault is removed. ? inrush curren t, start - u p time, output ho ld - u p time inrush current, inrush current is the first surge current seen on the input side when ac input is applied to the power supply. it is the first pulse captured. see below for the inrush current in a typical power supply. start - u p time, start - up time is measured from the point ac input is applied to the point output voltage reaches within 90% of its set value. see below for a typical start - up time characteristic. rise time, rise time is measured from the point output voltage rises from 10% to 90% of its set value. see below for a typical rise time measurement.
switch mode power supply drp024v 0 60w 1ba 10 / 13 rev: 00 , 1/10/2011 ho ld - u p time, hold time is the time when the ac input collapses and o/p voltage retains regulation for a certain period of time is called as hold up time. see in the picture below a typical hold up time characteristic of a power supply. the hold time is measured until t he output voltage remains in regulation hence it measured until the output voltage reaches min imum regulation - 2% of its set value. ? output voltage adjust the 24vdc connection is made using the "+" and " C " screw connections. at the time of deliv ery, the output voltage is 24v dc. the output voltage can be set from 2 4 to 28vdc on the potentiometer seen as adjust on the front panel of each power supply.
switch mode power supply drp024v 0 60w 1ba 11 / 13 rev: 00 , 1/10/2011 ? surge load see below typical surge load capability of the power supply, the psu is capable of delivering 3 secs of surge load about 150% of i o max the o/p voltage can be out of regulation limits of + 5%. ? dynamic load the p ower s upply is capable of dynamic output voltage load change from 10 % to 9 0% within 5% of regulation limits, a nd from 0% to 100% within 10% of regulation limits . see picture below on the dynamic behavior of the p ower supply .
switch mode power supply drp024v 0 60w 1ba 12 / 13 rev: 00 , 1/10/2011 ? redunda ncy & parallel operation with or ing diode see picture below for a typical redundant/parallel operation using cliq ii series power supplies. power supply unit 1 (psu1) and power supply unit 2 (psu2) are connected through a twin diode where anode 1 ( a1) is connected to the +ve of psu1 and a2 is connected to the +ve of psu2 and both output ground are shorted together. the output of psu1 and psu2 is drawn from the cathode k of the twin diode, making the power supply work in redundant/parallel operation . redundant operation: when 2 power supplies are connected in parallel, the power supply with the higher output voltage will take the maximum load while the other will operate in standby mode (at no load). in case the first power supply fails, the second will take over the load and supplies the required power to the end system.
switch mode power supply drp024v 0 60w 1ba 13 / 13 rev: 00 , 1/10/2011 parallel operation: when 2 power supplies are connected in parallel, they can share the load if the following steps are taken. step 1: measure the output voltages at no load from a1 to ground i.e. va1 to ground of psu1 and va2 to ground of psu2. if the voltages are not the same, follow step 2. if they are the same, skip to step 3. step 2: adjust the output voltages, with the help of vr on the power supply front panel market as adjust, to the same level. for e.g. if psu1 is measuring 24. 15vdc and psu2 is measuring 24 .25vdc, adjust the output voltage of one to be the same as the other. step 3: connect the power supply to the end system load and measure the output volt ages from a1 to ground i.e. va1 to ground of psu1 and va2 to ground of psu2. ensure that the output voltages are the same even after the 2 power supplies are connected to load. if not, adjust them with the vr available on the front panel. a tolerance of +/ - 25mv would be acceptable. note: 1 . if the output voltage of any power supply is higher, it will take the initial load and share the maximum load. 2 . if the output voltages are the same, then an equal load current sharing between the 2 power supplies can be achieved. 3 . the oring diode must be of an appropriate rating. the rating must be at least 4 times of the output load current and at least reverse voltage rating of 20vrr. 4 . the use of a heat sink is advised to ensure the oring diode does not overheat. 5 . recommended redundancy module : drr - 20a
mouser electronics authorized distributor click to view pricing, inventory, delivery & lifecycle information: delta: ? DRP024V060W1BA


▲Up To Search▲   

 
Price & Availability of DRP024V060W1BA

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X